Almaty
+7 771 781 00 60, +7 727 224 31 11
Сервис и зап.части +7 771 780 46 42
Astana
+7 771 780 46 48
info@akgen.kz


Language selection:

Disel generator
Aksa APD 12 A

Model : APD 12 A
Product : AKSA
CONTROL SYSTEM : DSE 6020
Introduction

Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.

Сertificate
  TS ISO 8528
  CE
  SZUTEST
  2000/14/EC
General Characteristics
Model Name APD 12 A
Frequency (Hz) 50
Fuel Type Diesel
Engine Made and Model AKSA - A3CRX14
Alternator Made and Model Aksa - AK 109 
Control Panel Model DSE 6020 
Canopy ANS 1
3 Phase, 50 Hz, PF 0.8
VOLTAGESTANDBY RATING (ESP) (ESP)PRIME RATING (PRP) (PRP)
kVAkWkVAkWAmp
400/231 11.5 9.20 10.6 8.48 16.60
STANDBY RATING (ESP) (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528. Overload is not allowed.

PRIME RATING (PRP) (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation,in accordance with ISO 3046.
Engine Specifications
Engine AKSA
Engine Model A3CRX14
NO. OF CYLINDERS AND BUILD 3 cylinders - in line
BORE AND STROKEmm 80 X 90
TOTAL DISPLACEMENTL 1,36
Aspiration Naturally Aspirated
COMPRESSION RATIO 18:1
RATED SPEED (RPM)d/dk 1500
OIL CAPACITYL 4
Standby Power (kW/HP) 12.8/17.16 kW
Prime Power (kW/HP) 11.7/15.68 kW
Block Heater QTY
  1
Block Heater Power (Watt)
  500
Fuel Type
  Diesel
Injection Type and System
  Direct
Type of Fuel Pump
  Direct
Governor System
  Mechanic
Operating Voltage (Vdc)
  12 Vdc
Battery and Capacity (Qty/Ah)
  1x36
Cooling Method
  Water Cooled
Cooling Fan Air Flow (m3/min)
  192
Coolant Capacity (engine only / with radiator) (lt)
  18,5
Air Filter
  Dry Type
Fuel Cons. Prime With %100 Load (lt/hr)
  3,4
Fuel Cons. Prime With %75 Load (lt/hr)
  2,6
Fuel Cons. Prime With %50 Load (lt/hr)
  1,7
Alternator Specifications
Manufacturer Aksa
Alternator Made and Model AK 109
Frequency (Hz)Hz 50
Power (kVA)kVA 11,3
DESIGN   Brushless
VOLTAGEV 400
Phase 3
A.V.R. SX460
Voltage Regulation(+/-) 1,5%
Insulation System H
Protection IP22
Rated Power Factor 0.8
COOLING AIR (m³/min)m3 4,26
Size and Weight
Open TypeDRY WEIGHT (kg.)
(kg.)
LENGHT
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
350 1400 760 927 32
CANOPYDRY WEIGHT (kg.)
(kg.)
LENGHT
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
ANS 1
470 1522 823 1127 32
Standart Specifications

Water cooled, Diesel engine 
Radiator with mechanical fan 
Protective grille for rotating and hot parts 
Electric starter and charge alternator 
Starting battery (with lead acid) including rack and cables 
Engine coolant heater 
Base frame design incorporates an integral fuel tank and anti-vibration isolators 
Flexible fuel connection hoses 
Single bearing, class H alternator 
Industrial exhaust silencer and steel bellows supplied separately(for open sets) 
Static battery charger 
Manual for application and installation

 

 

Optional Equpiments

ENGINE

  • Remote Radiator Cooling
  • Fuel-Water Seperator Filter

ALTERNATOR

  • Anti-Condensation Heater

CONTROL SYSTEM

  • Charge Ammeter

TRANSFER SWITCH

  • Three Pole Contactor
  • Four Pole Contactor
  • Three or four pole motor operated circuit breaker

OTHER ACCESSORIES

  • Main Fuel Tank
  • Automatic or manual fuel filling system
  • Manual oil drain pump
  • Residential silencer
  • Enclosure: weater protective or sound attenuated
  • Trailer
  • Tool kit for maintenance
Download
Get FREE expert advice in 15 minutes
Special offers