Disel generator
Aksa AC 66

Model : AC 66
Product : CUMMINS
CONTROL SYSTEM : DSE 6020
Introduction

Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.

Сertificate
  TS ISO 8528
  CE
  SZUTEST
  2000/14/EC
General Characteristics
Model Name AC 66
Frequency (Hz) 50
Fuel Type Diesel
Engine Made and Model CUMMINS - S3.8-G7
Alternator Made and Model Mecc Alte - ECP 32-2M/4 B 
Control Panel Model DSE 6020 
Canopy AK 40
3 Phase, 50 Hz, PF 0.8
VOLTAGESTANDBY RATING (ESP) (ESP)PRIME RATING (PRP) (PRP)
kVAkWkVAkWAmp
400/231 66 52.8 60 48.0 95.27
STANDBY RATING (ESP) (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528. Overload is not allowed.

PRIME RATING (PRP) (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation,in accordance with ISO 3046.
Engine Specifications
Engine CUMMINS
Engine Model S3.8-G7
NO. OF CYLINDERS AND BUILD 4 cylinders - in line
BORE AND STROKEmm 97 X 128
TOTAL DISPLACEMENTL 3.8
Aspiration Turbo Charged and After Cooled
COMPRESSION RATIO 17.5:1
RATED SPEED (RPM)d/dk 1500
OIL CAPACITYL 11
Standby Power (kW/HP) 64.9/87 kW
Prime Power (kW/HP) 59.6/79.9 kW
Block Heater QTY
  1
Block Heater Power (Watt)
  750
Fuel Type
  Diesel
Injection Type and System
  Direct
Type of Fuel Pump
  Bosh In-Line
Governor System
  Mechanic
Operating Voltage (Vdc)
  12 Vdc
Battery and Capacity (Qty/Ah)
  1x66
Charge Alternator (A)
  40
Cooling Method
  Water Cooled
Cooling Fan Air Flow (m3/min)
  116
Coolant Capacity (engine only / with radiator) (lt)
  7/16.5
Air Filter
  Dry Type
Fuel Cons. Prime With %100 Load (lt/hr)
  14.7
Fuel Cons. Prime With %75 Load (lt/hr)
  11
Fuel Cons. Prime With %50 Load (lt/hr)
  6.1
Alternator Specifications
Manufacturer Mecc Alte
Alternator Made and Model ECP 32-2M/4 B
Frequency (Hz)Hz 50
Power (kVA)kVA 63
DESIGN   Brushless
VOLTAGEV 400
Phase 3
A.V.R. DSR
Voltage Regulation(+/-) 1
Insulation System H
Protection IP23
Rated Power Factor 0.8
COOLING AIR (m³/min)m3 11.8
Size and Weight
Open TypeDRY WEIGHT (kg.)
(kg.)
LENGHT
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
1070 2150 1050 1516 240
CANOPYDRY WEIGHT (kg.)
(kg.)
LENGHT
(mm.)
WIDTH
(mm.)
HEIGHT
(mm.)
TANK CAPACITY (lt.) (Lt.)
AK 40
1320 3100 1113 1811 240
Standart Specifications

Water cooled, Diesel engine
Radiator with mechanical fan
Protective grille for rotating and hot parts
Electric starter and charge alternator
Starting battery (with lead acid) including rack and cables
Steel base frame and anti-vibration isolators
Base frame design incorporates an integral fuel tank and anti-vibration isolators
Flexible fuel connection hoses
Single bearing, class H alternator
Industrial exhaust silencer and steel bellows supplied separately
Static battery charger
Manual for application and installation

 

Optional Equpiments

ENGINE
• Fuel-Water Seperator Filter
• Low water level alarm
• Oil heater

ALTERNATOR
• Anti-Condensation Heater
• Over sized alternator
• Main line circuit breaker

CONTROL SYSTEM
• Remote annunciator panel
• Earth fault, single set
• Charge Ammeter

TRANSFER SWITCH
• Three or four pole contactor
• Three or four pole motor operated circuit breaker

OTHER ACCESSORIES
• Main Fuel Tank
• Automatic or manual fuel filling system
• Manual oil drain pump
• Low and high fuel level alarm
• Residential silencer
• Enclosure: weater protective or sound attenuated
• Duct adapter ( on radiator)
• Inlet and outlet motorised louvers
• Inlet and outlet acoustic baffles
• Trailer
• Tool kit for maintenance
• 1500/3000 hours maintenance kit
• Double wall chassis
• Supplied with oil and coolant - 30 °C
• Battery isolating switch

Download
Get FREE expert advice in 15 minutes
Special offers