Disel generator
Aksa APD 89C

Model : APD 89C
Product : AKSA
CONTROL SYSTEM : DSE 6120
Introduction

Sound-attenuated and weather protective enclosures for generating sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our modular designed sound insulated canopies (8 – 275kVA) fit directly to the open generator set to provide ease of access for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability.

Сertificate

- TS ISO 8528

- TS ISO 9001-2008

- CE - SZUTEST

- 2000/14/EC

General Characteristics

Model Name APD 89C

Frequency (Hz) 50

Fuel Type Diesel

Engine Made and Model CUMMINS 4BTA3.9-G11

Alternator Made and Mode AK 370

Control Panel Model 6120

Canopy ACM 5

3 Phase, 50 Hz, PF 0.8
VOLTAGE(V) Standby (ESP) Prime (PRP) Standby Aмпер
kVa kW kVa kW
400/231 71,20 89,00 62,40 78,00 129,26

Standby (ESP) Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source.ESP is in accordance with ISO 8528. Overload is not allowed.

Prime (PRP) Applicable for supplying power to varying electical load for unlimited hours. PRP is in accordance with ISO 8528. 10% overload capability is available for a period of 1 hour within 12-hour period of operation, in accordance with ISO 3046.

Engine Specifications

Engine CUMMINS

Engine Model 4BTA3.9-G11

Number of Cylinder(L) 4 cylinders - in line

Bore (mm) 102

Stroke(mm) 120

Displacement (lt) 3,9

Aspiration Turbo Charged&Aftercooled

Compression Ratio 17.3:1

RPM(d/dk) 1500

Oil Capacity (Total With Filter) (L) 10,9

Standby Power 80/107 APD 89C 

Prime Power 72/98.09

Block Heater QTY 1

Block Heater Power (Watt) 500

Fuel Type Diesel

Injection Type and System Direct

Type of Fuel Pump 6BB pump

Governor System Electronic

Operating Voltage (Vdc) 12 Vdc

Battery and Capacity (Qty/Ah) 1x54

Cooling method Water Cooled

Cooling Fan Air Flow (m3/min) 120

Coolant Capacity (engine only / with radiator) (lt) 9/20

Air Filter Dry Type

Fuel Cons.Prime With % 100 Load (lt/hr) 17.6

Fuel Cons.Prime With % 75 Load (lt/hr) 16.0

Fuel Cons.Prime With % 50 Load (lt/hr) 9.3

Alternator Specifications

Manufacturer AKSA

Alternator Made and Model AK 370

Frequency (Hz) 50

Power (kVA) 87.5

Voltage (V) 400

Phase 3 A.V.R. SX460

Voltage Regulation (+/-)1%

Insulation System H

Protection IP22

Rated Power Factor 0.8

Weight Comp.Generator (Kg) 126,75

Cooling Air (m3/min) 12,96

Size and Weight

Размеры генератора кабины

Length (mm) 2282

Width (mm) 1008

Hight (mm) 1532

Dry Weight (kg) 1300

Fuel Tank Capacity (L.) 180

 

Standart Specifications

Microprocessor controlled - 132x64 pixel LCD display makes information easy to read

- Front panel programming and also via PC software

- Soft touch membrane keypad and five key menu navigation

- Remote communications via USB, RS485 MODBUS

- Event logging (50) showing date and time

- Multiple date and time engine exercise mode and maintenance scheduler

- Engine block heater control

- Controls; stop, start, manuel, auto, mute lamb test/transfer to generator, transfer to mains, menu navigation.

Optional Equpiments

ENGINE

External radiator

Filter for separating water fraction from fuel

Heating oil

ALTERNATOR

Anti-condensation heater

Output circuit breaker

CONTROL SYSTEM

Automatic synchronization and power control system

Parallel system with external network

Synchronization system between the network

Remote Alarm Panel

Emergency engine stop

Remote control via modem

Ground connection point

Ammeter current

Load transfer panel

Three or four poles contactor

Three or four pole motor running switch

Other accessories

Charging current control

Automatic fuel pumping system

Manual oil drain pump

Fuel level sensors

Muffler

Enclosure: Protection against precipitation and noise reduction

Air duct adapter (in front of the radiator)

Supply and exhaust shutters with an electric drive

Noise suppression air chamber

Those. Kit (for maintenance)

Maintenance kit (1500/3000 hours)

Antifreeze and engine lubricating oil (when operating at - 30C)